Rockwell Automation SP600 User Manual Version 3.0 User Manual

Page 91

Advertising
background image

Using the Start-Up Routines on the LCD OIM

9-3

You do not have to configure all of the parameters in all 7 menus.
The first menu selection, Quickstart, contains the minimum basic
parameters that must be configured before running the drive. These
parameters are listed in table 9.1.

The drive’s default configuration assumes the following:

• US voltage class (202) = High voltage

• Motor nameplate base frequency (43) = 60 Hz

• Control mode (53) = Sensorless Vector

• Logic and Reference Source Select (89, 90) = Local OIM

Quickstart

If your application requires adjustment to parameters beyond those
listed in table 9.1, you can adjust the parameters in any or all of the
next 6 selections in the Start-Up menu, or you can adjust
parameters individually through the Parameters menu (see section
10.3).

Input Voltages

• 400/480 V

• 575 V

Motor Nameplate Data

• Motor Power Units

• Motor Power

• Motor FLA

• Motor Volts

• Motor Hertz

• Motor RPM

Table 9.1 – Quickstart Parameters

Parameter No.

Parameter Name

Default

155

Stop Mode A

Ramp

42

Motor NP FLA

Drive-dependent

81

Minimum Speed

0.0 Hz

82

Maximum Speed

60.0 Hz

140

Accel Time 1

10.0 sec

142

Decel Time 1

10.0 sec

90

Speed Ref A Sel

OIM

362

Digital In2 Sel

Start