Using the Start-Up Routines on the LCD OIM
9-3
You do not have to configure all of the parameters in all 7 menus.
The first menu selection, Quickstart, contains the minimum basic
parameters that must be configured before running the drive. These
parameters are listed in table 9.1.
The drive’s default configuration assumes the following:
• US voltage class (202) = High voltage
• Motor nameplate base frequency (43) = 60 Hz
• Control mode (53) = Sensorless Vector
• Logic and Reference Source Select (89, 90) = Local OIM
Quickstart
If your application requires adjustment to parameters beyond those
listed in table 9.1, you can adjust the parameters in any or all of the
next 6 selections in the Start-Up menu, or you can adjust
parameters individually through the Parameters menu (see section
10.3).
Input Voltages
• 400/480 V
• 575 V
Motor Nameplate Data
• Motor Power Units
• Motor Power
• Motor FLA
• Motor Volts
• Motor Hertz
• Motor RPM
Table 9.1 – Quickstart Parameters
Parameter No.
Parameter Name
Default
155
Stop Mode A
Ramp
42
Motor NP FLA
Drive-dependent
81
Minimum Speed
0.0 Hz
82
Maximum Speed
60.0 Hz
140
Accel Time 1
10.0 sec
142
Decel Time 1
10.0 sec
90
Speed Ref A Sel
OIM
362
Digital In2 Sel
Start