11-14

SP600 AC Drive User Manual

Enables/disables the compensation correction options.

Bit 0 - Reflect Wave

• Enables/disables reflected wave correction software, which

reduces overvoltage transients from the drive to the motor. For
lead lengths beyond 300 feet, enable this feature.

Bit 1 - Enable Jerk

• Enables/disables the jerk limit in the current limiter that helps to

eliminate overcurrent trips on fast accelerations. Disable this
feature if your application requires the actual acceleration of the
motor to be faster than .25 sec.

Bit 2 - Ixo AutoCalc

• Calculates voltage drop due to leakage inductance (see

parameter 64).