Rockwell Automation SP600 User Manual Version 3.0 User Manual

Page 120

Advertising
background image

11-18

SP600 AC Drive User Manual

Sets the boost level for steady state or deceleration when Fan/Pmp
V/Hz or Custom V/Hz modes are selected in Torque Perf Mode (53).

This boost level applies in the range from zero to break frequency
(Hz).

Sets the voltage the drive will output at Break Frequency (72).

Defines the volts per hertz ratio at break frequency. Applies only in
Fan/Pmp V/Hz or Custom V/Hz modes.

Sets the frequency at which Run Boost volts per hertz adaption
ends. Applies only in Fan/Pmp V/Hz or Custom V/Hz modes.

Sets the method of speed regulation.

• Open Loop provides no speed compensation due to load

variations. This is strict volts per hertz output as a function of the
speed reference.

70

Run Boost

Range:

0.0 to Motor NP Volts x 0.25 [0.1 VAC]

Default:

Motor HP Volts x 0.25

Access:

2

Path: Motor Control>Volts per Hertz

See also:

53, 69, 83

71

Break Voltage

Range:

0.0 to Motor NP Volts [0.1 VAC]

Default:

Motor NP Volts x 0.25

Access:

2

Path: Motor Control>Volts per Hertz

See also:

53, 72, 83

72

Break Frequency

Range:

0.0 to 400.0 [0.1 Hz]

Default:

Motor NP Freq x 0.25

Access:

2

Path: Motor Control>Volts per Hertz

See also:

53, 71, 83

80

Speed Mode

Range:

0 = Open Loop
1 = Slip Comp
2 = Process PI

Default:

0 = Open Loop

Access:

2

Path: Speed Command>Spd Mode & Limits

See also:

124 -138