Technical Specifications

A-1

A

PPENDIX

A

Technical Specifications

Table A.1 – Drive Monitoring and Limits

AC Input Overvoltage Trip

570 VAC/690 VAC (480 V/575 V Class)

AC Input Undervoltage Trip

280 VAC/345 VAC (480 V/575 V Class)

Bus Overvoltage Trip

810 VDC/1013 VDC (480 V/575 V Class)

Bus Undervoltage Trip

305 VDC/381 VDC (480 V/575 V Class)

Nominal Bus Voltage

648 VDC/810 VDC (480 V/575 V Class)

All Drives

Heat Sink Thermistor

Monitored by microprocessor overtemp trip

Drive Overcurrent Trip
Software Current Limit
Hardware Current Limit
Instantaneous Current Limit

20-150% of rated current
200% of rated current (typical)
220-300% of rated current (dependent on
drive rating)

Line Transients

up to 6000 volts peak per IEEE C62.41-1991

Control Logic Noise Immunity Showering arc transients up to 1500V peak

Power Ride-Thru

15 milliseconds at full load

Logic Control Ride-Thru

0.5 seconds minimum, 2 seconds typical

Ground Fault Trip

Phase-to-ground on drive output

Short Circuit Trip

Phase-to-phase on drive output

Intermittent Overload

110% overload capability for up to 1 minute.
150% overload capability for up to 3 seconds.

Current Limit Capability

Proactive Current Limit programmable from
20 to 150% of rated output current.
Independently programmable proportional
and integral gain.

Electronic Motor Overload
Protection

Class 10 protection with speed sensitive
response. Investigated by U.L. to comply with
N.E.C. Article 430. U.L. File E59272, volume
12.