Assigns an input function to the drive’s digital inputs.

1 = Enable: If the input is closed, the drive can run (start
permissive). If the input is open, the drive will not start.

If the drive is already running when this input is opened, the drive
will coast and indicate “not enabled” on the OIM (if present). This is
not considered a fault condition, and no fault will be generated.

If multiple enable inputs are configured, the drive will not run if any
of them are open.

2 = Clear Faults: This function allows an external device to reset
drive faults through the terminal block if Logic Source Sel (89) is set
to Terminal Blk or All Ports. An open-to-closed transition on this
input will reset the current fault (if any).

If this input is configured at the same time as Stop-Clear Faults,
then only the Clear Faults input can actually cause faults to be
reset.

3 = Function Loss: If the function loss input is open, a fault is
generated. The function loss input is active at all times regardless of
the selected logic control source.

5

To access Preset Speed 1, set Speed Ref A Sel to Preset Speed 1. See
table 11.3.

Table 11.6 – Speed Select Inputs

Speed Select Inputs

3

2

1

Reference Source

0

0

0

Speed Ref A Sel (90)

0

0

1

Preset Speed 1 (101)

0

1

0

Preset Speed 2 (102)

0

1

1

Preset Speed 3 (103)

1

0

0

Preset Speed 4 (104)

1

0

1

Preset Speed 5 (105)

1

1

0

Preset Speed 6 (106)

1

1

1

Preset Speed 7 (107)

Table 11.7 – Default Values for Parameters 361-366

Parameter No.

Default Value

361

4 = Stop - CF

362

5 = Start

363

3 = Function Loss

364

10 = Jog

365

18 = Auto/Man

366

15 = Speed Sel 1