12-20

SP600 AC Drive User Manual

Flashing yellow
Ready LED and
DigIn CflctB
indication on LCD
OIM.

Drive Status 2
(210) shows type 2
alarm(s).

Incorrect digital input
programming.

• Mutually exclusive

choices have been
made.

• 2-wire and 3-wire

programming may be
conflicting.

• Exclusive functions (i.e,

direction control) may
have multiple inputs
configured.

• Stop if factory default and

is not wired or is open.

• Start or Run

programming may be
missing.

Program Digital In”x” Sel
(361-366) to resolve
conflicts.

Remove multiple
selections for the same
function.

Install stop button to apply
a signal at stop terminal.

Table 12.9 – Drive Does Not Start From Terminal Block Logic

Indication(s)

Cause(s)

Corrective Action

Table 12.10 – Drive Does Not Start From OIM

Indication

Cause(s)

Corrective Action

None

Drive is programmed for
2-wire control and Logic
Source Sel (89) = All
Ports. OIM start and
network start are
disabled for 2-wire
control.

If 2-wire control is
required, no action is
necessary.

If 3-wire control is
required, program Digital
Inx Sel (361-366) for
correct inputs.

Flashing or steady red
Ready LED.

Active fault.

Reset fault.

Flashing yellow Ready
LED.

Enable input is open.

Close terminal block
enable input.

The terminal block stop
input is open and control
source is set to All
Ports.

Close terminal block stop
input.

Start inhibit bits are set. Check status in Start

Inhibits (214).