6 common symptoms and corrective actions – Rockwell Automation SP600 User Manual Version 3.0 User Manual
Page 215

Troubleshooting the Drive
12-19
12.6
Common Symptoms and Corrective Actions
Table 12.9 – Drive Does Not Start From Terminal Block Logic
Indication(s)
Cause(s)
Corrective Action
Flashing red
Ready LED.
Drive is faulted.
Clear fault:
• Press OIM stop key if
that OIM is control
source.
• Cycle power.
• Set Fault Clear (240) to
1.
• Toggle terminal block
stop or terminal block
reset digital input if
terminal block is the
control source.
Incorrect operation
from the terminal
block.
Incorrect input wiring.
• 2-wire control requires
Run, Run Forward, or
Run Reverse input(s).
• 3-wire control requires
Start and Stop inputs
• Jumper from terminal 7
to 8 is required.
Wire inputs correctly
and/or install jumper.
Incorrect digital input
programming.
• Mutually exclusive
choices have been
made.
• 2-wire and 3-wire
programming may be
conflicting.
• Exclusive functions (i.e,
direction control) may
have multiple inputs
configured.
• Stop if factory default and
is not wired or is open.
• Start or Run
programming may be
missing.
Program Digital In”x” Sel
(361-366) for correct
inputs.
Logic Source Sel is not set
to Terminal Blk.
Set Logic Source Sel to
Terminal Blk.