Aux in+ aux out – Rockwell Automation SP600 User Manual Version 3.0 User Manual

Page 62

Advertising
background image

5-2

SP600 AC Drive User Manual

!

ATTENTION: Unused wires in conduit must be grounded at
both ends to avoid a possible shock hazard caused by induced
voltages. Also, if a drive sharing a conduit is being serviced or
installed, all drives using this conduit should be disabled to
eliminate the possible shock hazard from cross-coupled motor
leads. Failure to observe these precautions could result in
bodily injury.

Figure 5.1 – Wire Routing and Terminal Block Locations (Frame 2 Shown)

BR1 B

SHLD

SHLD

V/T2 W/T3

PE R/L1 S/L2 T/L3

AUX IN+ AUX OUT–

Optional

Communications

Module

75C Cu Wire

6 AWG [10MM

2

] Max.

12 IN. LBS.
1.4 N-M

} TORQUE

WIRE
STRIP

CONTROL

POWER

Signal and Control
Terminal Block

Power
Terminal Block

I/O and Signal Wiring

Input Power Wiring

Motor Wiring

Terminal
Shield

(Frame 2 shown)