Troubleshooting the Drive

12-3

12.2

Determining Precharge Board Status Using the
LED Indicators (Frames 5 & 6 Only)

The precharge board LEDs are located above the Line Type jumper
shown in figure 12.2.

Figure 12.2 – Location of Precharge Status LED

Table 12.1 – Precharge Board LED Indicators

Name

Color

State

Description

Power
ON

Green

Steady

Indicates when pre-charge board power
supply is operational

Alarm

Yellow

Steady

Indicates one of the following alarms
occurred causing the pre-charge to
momentarily stop firing:

• Line Loss

• Low Phase (single-phase dropped

below 80% of line voltage)

• Input frequency out of range

(momentarily)

Note: An alarm condition automatically
resets when the condition no longer
exists

Fault

Red

Steady

Indicates one of the following faults:

• DC Bus short

• DC Bus not charged

• Input frequency out of range

• Overtemperature

Note: A fault indicates a malfunction that
needs to be corrected prior to restarting.
A fault condition is only reset after
cycling power.