Troubleshooting the Drive

12-21

.

Drive Status 1 (209)
indicates logic control
source.

Logic Source Sel (89) is
not equal to the desired
OIM (Local OIM, DPI
Port 2, or DPI Port 3).
DPI Port 2 is required
for remote OIM.

Verify setting of Logic
Source Sel (89). The OIM
Control digital input
effectively sets the control
source to the lowest
attached OIM port.

Table 12.10 – Drive Does Not Start From OIM (Continued)

Indication

Cause(s)

Corrective Action

Table 12.11 – Drive Does Not Respond to Changes in Speed Command

Indication

Cause(s)

Corrective Action

LCD OIM Status Line
indicates “At Speed”
and output is 0 Hz.

No value is coming from
the source of the
command.

1. If the source is an

analog input, check
wiring and use a meter
to check for presence
of signal.

2. Check Commanded

Freq (2) for correct
source.

None

Incorrect reference
source has been
programmed.

1. Check Speed Ref

Source (213) for the
source of the speed
reference.

2. Reprogram Speed Ref

A Sel (90) for correct
source.

None

Incorrect reference
source is being selected
via remote device or
digital inputs.

1. Check Drive Status 1

(209), bits 12 - 15 for
unexpected source
selections.

2. Check Dig In Status

(216) to see if inputs
are selecting an
alternate source.

3. Reprogram digital

inputs to correct Speed
Sel x option.

Speed reference from
analog input

Improper reference
common signal wiring.

1. Verify that common is

properly connected to
AnlgIn(-) terminal.