Sets the reaction to a loss of input power. Power loss is recognized
when:

DC bus voltage is

≤ 73% of DC Bus Memory and Power Loss Mode

is set to Coast.

DC bus voltage is

≤ 82% of DC Bus Memory and Power Loss Mode

is set to Decel.

Sets the time that the drive will remain in power loss mode before a
fault is issued.

Sets the level at which the Power Loss Mode (184) selection will
occur.

184

Power Loss Mode

Range:

0 = Coast
1 = Decel
2 = Continue
3 = Coast input
4 = Decel input

Default:

0 = Coast

Access:

1

Path: Dynamic Control>Stop/Power Loss

See also:

184

185

Power Loss Time

Range:

0.0 to 60.0 Sec [0.1 Sec]

Default:

0.5 Sec

Access:

1

Path: Dynamic Control>Stop/Power Loss

See also:

184

186

Power Loss Level

Range:

0.0 to 999.9 V [0.1 V]

Default:

0.0 V

Access:

2

Path: Dynamic Control>Power Loss

See also:

184