Rockwell Automation SP600 User Manual Version 3.0 User Manual
Page 152
![background image](/manuals/580884/152/background.png)
11-50
SP600 AC Drive User Manual
Sets the reaction to a loss of input power. Power loss is recognized
when:
DC bus voltage is
≤ 73% of DC Bus Memory and Power Loss Mode
is set to Coast.
DC bus voltage is
≤ 82% of DC Bus Memory and Power Loss Mode
is set to Decel.
Sets the time that the drive will remain in power loss mode before a
fault is issued.
Sets the level at which the Power Loss Mode (184) selection will
occur.
184
Power Loss Mode
Range:
0 = Coast
1 = Decel
2 = Continue
3 = Coast input
4 = Decel input
Default:
0 = Coast
Access:
1
Path: Dynamic Control>Stop/Power Loss
See also:
184
185
Power Loss Time
Range:
0.0 to 60.0 Sec [0.1 Sec]
Default:
0.5 Sec
Access:
1
Path: Dynamic Control>Stop/Power Loss
See also:
184
186
Power Loss Level
Range:
0.0 to 999.9 V [0.1 V]
Default:
0.0 V
Access:
2
Path: Dynamic Control>Power Loss
See also:
184