11-24

SP600 AC Drive User Manual

Scales the upper value of the Speed Ref Sel (90) selection when
the source is an analog input. This value corresponds to the value
entered in parameter 322 or 324.

Scales the lower value of the Speed Ref A Sel (90) selection when
the source is an analog input. This value corresponds to the value
entered in parameter 323 or 325.

Specifies the manual speed reference source when a digital input is
configured for manual selection. See parameters 361 to 366.

Scales the upper value of the TB Man Ref Sel selection when the
source is an analog input. This parameter should be set in
conjunction with parameter 322 or 325, depending on the analog
input being used.

91

Speed Ref A Hi

Range:

-/+ Maximum Speed [0.1 Hz]

Default:

Maximum Speed

Access:

1

Path: Speed Command>Speed References

See also:

82, 322, 324

92

Speed Ref A Lo

Range:

-/+ Maximum Speed [0.1 Hz]

Default:

0.0 Hz

Access:

1

Path: Speed Command>Speed References

See also:

81, 323, 325

96

TB Man Ref Sel

Range:

1 = Analog In 1
2 = Analog In 2
3-8 = Reserved
9 = MOP Level

Default:

2 = Analog In 2

Access:

1

Path: Speed Command>Speed References

See also:

97, 98

97

TB Man Ref Hi

Range:

-/+Maximum Speed [0.1 Hz]

Default:

Maximum Speed

Access:

1

Path: Speed Command>Speed References

See also:

96, 322, 324