SP600 AC Drive User Manual

12.8.1 Accessing the Fault Queue

As described in section 12.5.1, the drive automatically retains a
history of the last eight faults that have occurred in the fault queue.

To access the fault queue, press the F4 key at the process display
screen, or see figure 12.5 to access the fault queue from the Main
Menu.

The drive can be reset (as if the power were cycled) by pressing the
F3 (Dres) function key while in the "View Fault Queue" screens.
The reset function is active only while the drive is stopped. During a
reset, drive communication with peripheral devices will stop until the
reset function completes.

Figure 12.5 – Accessing the Fault Queue

Figure 12.6 – Sample Fault Queue Entry

!

ATTENTION: Pressing F3 (Dres) will immediately
cause the drive to be reset. This may result in
communication errors in other devices attached to
the drive which could result in machine damage.

Diagnostics:

Device Version

OIM Version

View Fault Queue

P0: SP600

Stopped Auto

Main Menu

Diagnostics

FltQ# : F#xxxxx
Fault Text String
Accum:
hours:min:sec

1

Cflt

Clrqu

Dres

Highlight Diagnostics icon

Highlight item

Monitor

Lang

F1 = Clear fault*

FltQ# : F#xxxxx
Fault1 Text String
Accum:
hours:min:sec

1

Cflt

Clrqu

Dres

FltQ# : F#xxxxx
Fault2 Text String
Accum:
hours:min:sec

2

Cflt

Clrqu

Dres

F2

F1

F2 = Clear fault queue

F3

F3 = Drive Reset

*

Appears only when fault is active.