Finding Wire-Routing Locations and Grounding

5-3

Figure 5.2 – Wire Routing and Terminal Block Locations (Frame 5 Shown)

WIRE RANGE: 14-1/0 AWG (2.5-35 MM

2

)

TORQUE: 32 IN-LB (3.6 N-M)
STRIP LENGTH: 0.67 IN (17 MM)
USE 75

° C CU WIRE ONLY

POWER TERMINAL RATINGS

WIRE RANGE: 6-1/0 AWG (16-35 MM

2

)

TORQUE: 44 IN-LB (5 N-M)
STRIP LENGTH: 0.83 IN (21 MM)

GROUND TERMINAL RATINGS (PE)

300 VDC EXT PWR SPLY TERM (PS+, PS-)

WIRE RANGE: 22-10 AWG (0.5-4 MM

2

)

TORQUE: 5.3 IN-LB (0.6 N-M)
STRIP LENGTH: 0.35 IN (9 MM)

17

21

INPUT AC

OUTPUT

Optional

Communications

Module

9

60 to 75 HP

100 HP

Input Power Wiring

Motor Wiring

I/O and Signal
Wiring

I/O and Signal
Wiring

Terminal
Shield

Power Terminal
Block

Signal and Control
Terminal Block