Parameter Descriptions

11-35

The present state of the process PI regulator.

See parameter 125 for control of the PI functions.

Bit 0 - PI Enabled

• Indicates whether or not the process PI loop is enabled.

Bit 1 - PI Hold

• Is set to 1 to indicate when a digital input is configured for PI

Hold and is turned on, or the PI Hold bit is set in PI Control
(125).

Bit 2 - PI Reset

• Is set to 1 to indicate when the PI Integrator is being reset to

zero.

Bit 3 - PI InLimit

• Is set to 1 to indicate when the PI output equals positive limit

or negative limit.

Present value of the process PI reference signal.

134

PI Status

Range:

See figure 11.13

Default:

Read Only

Access:

2

Path: Speed Command>Process PI

See also:

80, 124-138

Figure 11.13 – PI Status (134)

0

0

0

0

x

x

x

x

x

x

x

x

x

x

x

x

10

0

1

2

3

4

5

6

7

8

9

11

12

13

14

15

1 =Condition True
0 =Condition False
x =Reserved

Bit #

PI Enabled

PI Hold

PI Reset

PI InLimit

Nibble 1

Nibble 2

Nibble 3

Nibble 4

135

PI Ref Meter

Range:

-/+100.00% [0.01%]

Default:

Read Only

Access:

2

Path: Speed Command>Process PI

See also:

80, 124 - 138