11-70

SP600 AC Drive User Manual

The output of the logic function control block resulting from the
combination of all port requests and masking functions. Each bit or
set of bits represent a command to the drive.

Present frequency reference scaled as a DPI reference for peer-to-
peer communications. The value shown is the output prior to the
accel/decel ramp and any corrections supplied by slip comp, PI, etc.

271

Drive Logic Rslt

Range:

See figure 11.31

Default:

Read Only

Access:

2

Path: Communication>Comm Control

See also:

Figure 11.31 – Drive Logic Rslt (271)

0

1

1

0

0

0

0

1

0

1

1

1

0

0

0

0

10

0

1

2

3

4

5

6

7

8

9

11

12

13

14

15

1 =Condition Active
0 =Condition Inactive
x =Reserved

Bit #

Stop

Star

t

Jog

Clear F

ault

Forw

ard

Re

verse

Local Contr

l

Mop Inc

Accel 1

Accel 2

Decel 1

Decel 2

Spd Ref ID 0

(1)

Spd Ref ID 1

(1)

Spd Ref ID 2

(1)

MOP Dec

Nibble 1

Nibble 2

Nibble 3

Nibble 4

Bits

(1)

Description

14

13

12

0
0
0
0
1
1
1
1

0
0
1
1
0
0
1
1

0
1
0
1
0
1
0
1

No Command - Man. Mode
Ref A Auto
Preset 2 Auto
Preset 3 Auto
Preset 4 Auto
Preset 5 Auto
Preset 6 Auto
Preset 7 Auto

272

Drive Ref Rslt

Range:

0 to 32767 [1]

Default:

Read Only

Access:

2

Path: Communication>Comm Control

See also:

Advertising