Aux in+ aux out, Ps+ ps – Rockwell Automation SP600 User Manual Version 3.0 User Manual

Page 34

Advertising
background image

About the Drive

2-20

Figure 2.4 – Drive Connections

BR1 B

SHLD

SHLD

V/T2 W/T3

PE R/L1 S/L2 T/L3

AUX IN+ AUX OUT–

Optional

Communications

Module

75C Cu Wire

6 AWG [10MM

2

] Max.

12 IN. LBS.
1.4 N-M

} TORQUE

WIRE
STRIP

CONTROL

POWER

Frame 2

WIRE RANGE: 14-1/0 AWG (2.5-35 MM2)
TORQUE: 32 IN-LB (3.6 N-M)
STRIP LENGTH: 0.67 IN (17 MM)
USE 75

° C CU WIRE ONLY

POWER TERMINAL RATINGS

WIRE RANGE: 6-1/0 AWG (16-35 MM2)
TORQUE: 44 IN-LB (5 N-M)
STRIP LENGTH: 0.83 IN (21 MM)

GROUND TERMINAL RATINGS (PE)

300 VDC EXT PWR SPLY TERM (PS+, PS-)

WIRE RANGE: 22-10 AWG (0.5-4 MM2)
TORQUE: 5.3 IN-LB (0.6 N-M)
STRIP LENGTH: 0.35 IN (9 MM)

17

21

INPUT AC

OUTPUT

Optional

Communications

Module

9

Frame 5

Optional

Communications

Module

L2

L1

T3

T2

T1

L3

INPUT

OUTPUT

USE 75 C

COPPER WIRE

ONLY

TORQUE
52 IN-LB

(6 N-M)

BR2

PS+

PS–

BR1

DC+

DC–

USE 75 C COPPER WIRE ONLY, TORQUE 52 IN-LB (6 N-M)

22-10
AWG

5.3 IN-LB
(0.6 N-M)

WIRE STRIP

Frame 6

BR1 BR2 DC+ DC- U/T1 V/T2 W/T3 R/L1 S/L2

T/L3

Optional

Communications

Module

PE B

PE A

75C Cu Wire

3 AWG [25MM

2

] Max.

16 IN. LBS.
1.8 N-M

} TORQUE

WIRE
STRIP

CONTROL

POWER

AUX IN

+ –

SHLD

SHLD

PE

75C Cu Wire

6 AWG [10MM2] Max.

BR1 BR2

12 IN. LBS.
1.4 N-M

} TORQUE

Frames 3 & 4

Advertising