3.1.2 Making Sure Environmental Conditions are Met

Before deciding on an installation site, consider the following
guidelines:

Verify that NEMA 1 drives can be kept clean, cool, and dry.

The area chosen should allow the space required for proper air
flow as defined in section 3.1.3.

Be sure that NEMA 1 drives are away from oil, coolants, or other
airborne contaminants.

Do not install the drive more than 3300 feet above sea level
without derating output power. For every 300 feet above 3300
feet, derate the output current 1%.

Verify that the drive location will meet the environmental
conditions in Appendix A.

Figure 3.2 – Selecting Input Phase and Fan Voltage (60HP and Larger)

480 Volt Tap

600 Volt Tap

690 Volt Tap

400 Volt Tap

WIRE RANGE: 14-1/0 AWG (2.5-35 MM2)
TORQUE: 32 IN-LB (3.6 N-M)
STRIP LENGTH: 0.67 IN (17 MM)
USE 75

° C CU WIRE ONLY

POWER TERMINAL RATINGS

WIRE RANGE: 6-1/0 AWG (16-35 MM2)
TORQUE: 44 IN-LB (5 N-M)
STRIP LENGTH: 0.83 IN (21 MM)

GROUND TERMINAL RATINGS (PE)

300 VDC EXT PWR SPLY TERM (PS+, PS-)

WIRE RANGE: 22-10 AWG (0.5-4 MM2)
TORQUE: 5.3 IN-LB (0.6 N-M)
STRIP LENGTH: 0.35 IN (9 MM)

17

21

INPUT AC

OUTPUT

Optional

Communications

Module

9

Line Type

Three-Phase

(def

ault)

Single-Phase

Spare

Spare

x 4