11-80

SP600 AC Drive User Manual

Selects the mode for the analog output.

Selects whether the signed value or absolute value of a parameter
is used before being scaled to drive the analog output.

340

Anlg Out Config

Range:

See figure 11.37

Default:

0

Access:

1

Path: Inputs & Outputs>Analog Outputs

See also:

Figure 11.37 – Analog Out Config

x

x

x

0

x

x

x

x

x

x

x

x

x

x

x

x

10

0

1

2

3

4

5

6

7

8

9

11

12

13

14

15

1 =Current
0 =Voltage
x =Reserved

Bit #

Factory Default Bit Values

Analog Out1

341

Anlg Out Absolut

Range:

See figure 11.38

Default:

See figure 11.38

Access:

2

Path: Inputs & Outputs>Analog Outputs

See also:

342

Figure 11.38 – Anlg Out Absolute (341)

x

x

x

1

x

x

x

x

x

x

x

x

x

x

x

x

10

0

1

2

3

4

5

6

7

8

9

11

12

13

14

15

1 =Absolute
0 =Signed
x =Reserved

Bit #

Factory Default Bit Values

Analog Out1

Bit

Signal Level

Output Volts

0

-100%
0%
100%

0 V
5 V
10 V

1

-100%
0%
100%

10 V
0 V
10 V