Rockwell Automation SP600 User Manual Version 3.0 User Manual

Page 180

Advertising
background image

11-78

SP600 AC Drive User Manual

Selects drive response when an analog signal loss is detected.
(1.6V = signal loss, 1.9V = end of signal loss; 3.2 mA = signal loss,
3.8 mA = end of signal loss.)

One of the selections (1=Fault) stops the drive on signal loss. All
other choices make it possible for the input signal to return to a
usable level while the drive is still running.

Important:

Note that there is no signal loss detection while the
input is in bipolar voltage mode.

Sets the highest input value to the analog input 2 scaling block. See
parameter 322 for an example.

324

Analog In 1 Loss

Range:

0 = Disabled
1 = Fault
2 = Hold Input (use last frequency command)
3 = Set Input Lo (use Minimum Speed as frequency
command)
4 = Set Input Hi (use Maximum Speed as frequency
command)
5 = Goto Preset1 (use Preset 1 as frequency
command)
6 = Hold OutFreq (maintain last output frequency)

Default:

0 = Disabled

Access:

2

Path: Inputs & Outputs>Analog Inputs

See also:

91, 92

!

ATTENTION: Setting parameter 324 to a value
other than 1 allows the drive to continue running or
resume running if a signal loss occurs. If a lost
analog signal is restored while the drive is running,
the drive will ramp to the restored reference level at
the rate specified in Accel Time 1 (140), Accel Time
2 (141), Decel Time 1 (142), and Decel Time 2 (143).
Be aware that an abrupt speed change may occur
depending upon the new reference level and the rate
specified in these parameters. Failure to observe
this precaution could result in bodily injury.

325

Analog In 2 Hi

Range:

4.000 to 20.000 mA [0.001 mA]
-/+10.0 V [0.1 V]
0.0 to 10.0 V [0.1 V]

Default:

10 V

Access:

2

Path: Inputs & Outputs>Analog Inputs

See also:

91, 92, 320

Advertising