Parameter Descriptions

11-71

Present frequency reference scaled as a DPI reference for peer-to-
peer communications. The value shown is the value after the accel/
decel ramp but prior to any corrections supplied by slip comp, PI,
etc.

Disables manual mode activation from the port corresponding to bit
number.

Example:

Bit 0 = 0 Terminal block disabled
Bit 1 = 1 Local OIM enabled

In this example, manual mode can be selected by the OIM but not
by terminal block inputs.

273

Drive Ramp Rslt

Range:

0 to 32767 [1]

Default:

Read Only

Access:

2

Path: Communication>Comm Control

See also:

286

Manual Mask

Range:

See figure 11.32

Default:

0x2F

Access:

2

Path: Communication>Masks & Owners

See also:

Figure 11.32 – Manual Mask (286)

1

1

1

1

x

1

x

x

x

x

x

x

x

x

x

x

10

0

1

2

3

4

5

6

7

8

9

11

12

13

14

15

1 = Control is Enabled
0 = Control is Disabled
x =Reserved

Bit #

Factory Default Bit Values

Te

rminal Blk

Local OIM

DPI P

or

t 2

DPI P

or

t 3

Reser

ve

d

Netw

or

k

Reser

ve

d

Nibble 1

Nibble 2

Nibble 3

Nibble 4