Rockwell Automation SP600 User Manual Version 3.0 User Manual

Page 185

Advertising
background image

Parameter Descriptions

11-83

361
362
363
364
365
366

Digital In1 Sel
Digital In2 Sel
Digital In3 Sel
Digital In4 Sel
Digital In5 Sel
Digital In6 Sel

Range:

0 = Not Used
1 = Enable
2 = Clear Faults

1

3 = Function Loss
4 = Stop - CF

2

5 = Start
6 = Fwd/Reverse

3

7 = Run

4

8 = Run Forward

4

9 = Run Reverse

4

10 = Jog

3

11 = Jog Forward
12 = Jog Reverse
13 = Stop Mode B
14 = Bus Reg Md B
15 = Speed Sel 1

5

16 = Speed Sel2

5

17 = Speed Sel 3

5

18 = Manual
19 = Reserved
20 = Acc2 & Dec2
21 = Accel 2
22 = Decel 2
23 = MOP Inc
24 = MOP Dec
25 = OIM Control
26 = PI Enable
27 = PI Hold
28 = PI Reset
29 = Pwr Loss Lvl
30 = Precharge En
31 - 38 = Reserved
39 = UserSetBit0
40 = UserSetBit1

Default:

See table 11.7

Access:

1

Path: Inputs & Outputs>Digital Inputs

See also:

96, 100, 124, 140, 156, 162, 194, 380

1

When Digital In”x” Sel is set to option 2 (Clear Faults), the stop key cannot
be used to clear a fault condition.

2

Stop -CF may be used for 2 wire functions. See #4 below.

3

Typical 3-Wire Inputs. These require that only 3-wire functions are chosen.
Including 2-Wire selections will cause a type 2 alarm.

4

Typical 2-Wire Inputs. These require that only 2-wire functions are chosen.
Including 3-wire selections will cause a type 2 alarm.