Parameter Descriptions

11-25

.

Scales the lower value of the TB Man Ref Sel selection when the
source is an analog input. This parameter should be set in
conjunction with parameter 323 or 326, depending on the analog
input being used.

Sets the output frequency when a jog command is issued. The jog
function can be activated using the OIM or terminal block
assignments.

Provides an internal fixed speed command value when
Speed Ref A = Preset Spd 1-7. The preset speed is selected by the
configuration of the Dig In # speed select functions.

98

TB Man Ref Lo

Range:

-/+Maximum Speed [0.1 Hz]

Default:

0.0 Hz

Access:

1

Path: Speed Command>Speed References

See also:

96, 323, 325

100

Jog Speed

Range:

0 to Maximum Speed [0.1 Hz]

Default:

10.0 Hz

Access:

0

Path: Speed Command>Discrete Speeds

See also:

101
102
103
104
105
106
107

Preset Speed 1
Preset Speed 2
Preset Speed 3
Preset Speed 4
Preset Speed 5
Preset Speed 6
Preset Speed 7

Range:

-/+ Maximum Speed [0.1 Hz]

Default:

See table 11.2

Access:

2

Path: Speed Command>Discrete Speeds

See also:

90, 93

Table 11.2 – Default Values for Preset Speeds 1-7

Parameter No.

Parameter Name

Default

101

Preset Speed 1

5.0 Hz

102

Preset Speed 2

10.0 Hz

103

Preset Speed 3

20.0 Hz

104

Preset Speed 4

30.0 Hz

105

Preset Speed 5

40.0 Hz

106

Preset Speed 6

50.0 Hz

107

Preset Speed 7

60.0 Hz