Rockwell Automation SP600 User Manual Version 3.0 User Manual
Page 138
11-36
SP600 AC Drive User Manual
Present value of the process PI feedback signal.
Present value of the process PI error signal.
Present value of the process PI output signal.
The Accel Time parameters set the rate at which the drive ramps to
its output frequency after a start command or during an increase in
command frequency (speed change). The rate established is the
result of the following equation: Maximum Frequency - Minimum
Frequency / Accel Time = Accel Rate
Two accel times exist to enable acceleration rate changes “on the
fly” using a building automation system command, digital input, or
F-Key, if configured (see Appendix B).
136
PI Fdback Meter
Range:
-/+100.00% [0.01%]
Default:
Read Only
Access:
2
Path: Speed Command>Process PI
See also:
80, 124 - 138
137
PI Error Meter
Range:
-/+100.00% [0.01%]
Default:
Read Only
Access:
2
Path: Speed Command>Process PI
See also:
80, 124 - 138
138
PI Output Meter
Range:
-/+Maximum Freq [0.1 Hz]
Default:
Read Only
Access:
2
Path: Speed Command>Process PI
See also:
80, 124 - 138
PI Output
PI Error
PI Prop Gain
PI Error
PI Integral Time
---------------------------------------
+
×
≅
140
141
Accel Time 1
Accel Time 2
Range:
0.1 to 3600.0 sec [0.1 sec]
Default:
10.0 sec
Access:
140=0
141=2
Path: Dynamic Control>Ramp Rates
See also:
56, 142, 143, 146, 361-366