Rockwell Automation SP600 User Manual Version 3.0 User Manual
Page 166

11-64
SP600 AC Drive User Manual
Accumulated percentage of motor overload. Continuously operating
the motor over 100% of the motor overload setting will increase this
value to 100% and cause a drive fault.
Captures and displays the output frequency of the drive at the time
of the last fault.
Captures and displays motor amps at the time of the last fault.
Captures and displays the DC bus voltage of the drive at the time of
the last fault.
220
Motor OL Count
Range:
0.0 to 100.0 % [1.0%]
Default:
Read Only
Access:
2
Path: Utility>Diagnostics
See also:
47, 48
224
Fault Frequency
Range:
0.0 to +/-400.0 Hz [0.1 Hz]
Default:
Read Only
Access:
2
Path: Utility>Diagnostics
See also:
225-230
225
Fault Amps
Range:
0.0 to Rated Amps x 2 [0.1 Amps]
Default:
Read Only
Access:
2
Path: Utility>Diagnostics
See also:
224-230
226
Fault Bus Volts
Range:
0.0 to Max Bus Volts [0.1 VDC]
Default:
Read Only
Access:
2
Path: Utility>Diagnostics
See also:
224-230