Accumulated percentage of motor overload. Continuously operating
the motor over 100% of the motor overload setting will increase this
value to 100% and cause a drive fault.

Captures and displays the output frequency of the drive at the time
of the last fault.

Captures and displays motor amps at the time of the last fault.

Captures and displays the DC bus voltage of the drive at the time of
the last fault.

220

Motor OL Count

Range:

0.0 to 100.0 % [1.0%]

Default:

Read Only

Access:

2

Path: Utility>Diagnostics

See also:

47, 48

224

Fault Frequency

Range:

0.0 to +/-400.0 Hz [0.1 Hz]

Default:

Read Only

Access:

2

Path: Utility>Diagnostics

See also:

225-230

225

Fault Amps

Range:

0.0 to Rated Amps x 2 [0.1 Amps]

Default:

Read Only

Access:

2

Path: Utility>Diagnostics

See also:

224-230

226

Fault Bus Volts

Range:

0.0 to Max Bus Volts [0.1 VDC]

Default:

Read Only

Access:

2

Path: Utility>Diagnostics

See also:

224-230