Parameter Descriptions

11-93

384

Digital Out1 Sel

Range:

1 = Fault

1

- A fault has occurred and stopped the drive

2 = Alarm

1

- A Type 1 or Type 2 alarm condition exists

3 = Ready - The drive is powered, Enabled and no start

inhibits exist. It is “ready” to run

4 = Run - The drive is outputting voltage and frequency to

the motor (indicates 3–wire control, either direction)

5 = Forward Run - The drive is outputting voltage and

frequency to the motor (indicates 2–wire control in
forward)

6 = Reverse Run - The drive is outputting voltage and

frequency to the motor (indicates 2–wire control in
reverse)

7 = Auto Restart - The drive is currently executing the

Auto Restart or “Run at Power Up” function

8 = Reserved
9 = At Speed - The output frequence equals the

commanded speed

10 = At Freq

2

- The drive output frequency equals or

exceeds the programmed limit

11 = At Current

2

- The drive total output current exceeds

the programmed limit

12 = At Torque

2

- The drive output torque current

component exceeds the programmed limit

13 = At Temp

2

- The drive operating temperature exceeds

the programmed limit

14 = At Bus Volts

2

- The drive bus voltage exceeds the

programmed limit

15 = At PI Error

2

- The drive Process PI Loop error

exceeds the programmed limit

16 = DC Braking - The drive is currently executing either a

“DC Brake” or a “Ramp to Hold” stop command and
the DC braking voltage is still being applied to the
motor.

17 = Curr Limit - The drive is currently limiting output

current

18 = Economize - The drive is currently reducing the

output voltage to the motor to attempt to reduce
energy costs during a lightly loaded situation.

19 = Motor Overld - The drive is currently reducing the

output voltage to the motor to attempt to reduce
energy costs during a lightly loaded situation.

20 = Power Loss - The drive has monitored DC bus

voltage and sensed a loss of input AC power that
caused the DC bus voltage to fall below the fixed
monitoring value (82% of DC bus Memory (13))

21 = Input 1 Link - The digital input value is output on

Dig Out1

22 = Input 2 Link
23 = Input 3 Link
24 = Input 4 Link
25 = Input 5 Link
26 = Input 6 Link
27 = TB in Manual - The terminal block has manual

reference control

Default:

4 = Run

Access:

1

Path: Inputs & Output>Digital Outputs