Rockwell Automation SP600 User Manual Version 3.0 User Manual
Page 230

A-6
SP600 AC Drive User Manual
Selectable Motor Control
Sensorless Vector with full tuning. Standard
V/Hz with full custom capability.
Stop Modes
Multiple programmable stop modes including
Ramp, Coast, DC-Brake, Ramp-to-Hold and
S-curve.
Accel/Decel
Two independently programmable accel and
decel times. Each time may be programmed
from 0 - 3600 seconds in 0.1 second
increments.
Table A.5 – Control Specifications
Table A.6 – Analog Interface Specifications
Analog Input 1,
Differential Voltage Input
Signal level
Differential Input resistance
Isolation
Resolution
Input processing period
-10V to +10V
100k
Ω
160V
11 bits plus sign
5ms
Analog Input 1,
Differential Current Input
Signal level
Differential Input resistance
Resolution
Input processing period
0(4) to 20mA
124
Ω
11 bits plus sign
5ms
Analog Input 2,
Differential Voltage Input
Signal level
Differential Input resistance
Initial accuracy (@25°C)
Resolution
Input processing period
-10V to +10V
100k
Ω
160V
11 bits plus sign
5ms
Analog Input 2,
Differential Current Input
Signal level
Differential Input resistance
Resolution
Input processing period
0(4) to 20mA
124
Ω
11 bits plus sign
5ms