Wiring Requirements for the Drive

4-3

4.1.1 Power Wire Sizes

Input power wiring should be sized according to applicable codes to
handle the drive’s continuous-rated input current. Output wiring
should be sized according to applicable codes to handle the drive’s
continuous-rated output current. See table 4.2 for the range of
power wire sizes that the terminals can accommodate.

Table 4.1 – Recommended Shielded Wire

Location

Rating/Type

Description

Standard
(Option 1)

600V, 90°C (194°F)
XHHW2/RHW-2
Anixter
B209500-B209507,
Belden 29501-29507,
or equivalent

• Four tinned copper conductors with XLPE
insulation.
• Copper braid/aluminum foil combination
shield and tinned copper drain wire.
• PVC jacket.

Standard
(Option 2)

Tray rated 600V, 90° C
(194° F) RHH/RHW-2
Anixter OLF-7xxxxx or
equivalent

• Three tinned copper conductors with XLPE
insulation.
• 5 mil single helical copper tape (25%
overlap min.) with three bare copper
grounds in contact with shield.
• PVC jacket.

Class I & II;
Division I & II

Tray rated 600V, 90° C
(194° F) RHH/RHW-2
Anixter 7V-7xxxx-3G
or equivalent

Three bare copper conductors with XLPE

insulation and impervious corrugated

continuously welded aluminum armor.

• Black sunlight resistant PVC jacket
overall.
• Three copper grounds on #10 AWG and
smaller.

Table 4.2 – Power Terminal Block Specifications

Frame

Wire Size Range

1

Torque

Maximum Minimum

2

6 AWG

18 AWG

1.4 to 1.7 N-m (12 to 15 in-lb)

3

3 AWG

14 AWG

1.8 to 3.8 N-m (16 to 32 in-lb)

4

1/0 AWG

8 AWG

4.0 N-m (12 in-lb)

5 (60 to 75 HP)

1/0 AWG

12 AWG

(2)

5 (100 HP)

2/0 AWG

4 AWG

(2)

6

4/0 AWG

14 AWG

6.0 N-m (52 in-lb)

1

Maximum/minimum sizes that the terminal block will accept. These are not
recommendations.

2

Refer to terminal block label inside drive.