Rockwell Automation SP600 User Manual Version 3.0 User Manual

Page 75

Advertising
background image

Installing Control Wiring

7-3

Table 7.1 – Wiring Signal and Control I/O to the Terminal Block

No.

Signal

Factory

Default

Description

Relate

d

P

a

ram.

Analog Inputs

1

Anlg Volts In 1 (–)

1

Isolated

2

, bipolar, differential,

±10

V, 11 bit & sign, 100k ohm input
impedance.

320 -
329

2

Anlg Volts In 1 (+)

3

Anlg Volts In 2 (–)

1

Isolated

3

, bipolar, differential,

±10

V, 11 bit & sign, 100k ohm input
impedance.

4

Anlg Volts In 2 (+)

5

Potentiometer
Common

For (+) and (–) 10 V pot
references.

Analog Output

6

Anlg Volts Out 1 (–) Output

Freq

1

Bipolar, differential,

±10 V, 11 bit

& sign, 2k ohm minimum load.

340 -
344

7

Anlg Volts Out 1 (+)

8

Anlg Current Out 1
(–)

1

4-20 mA, 11 bit & sign, 400 ohm
maximum load.

9

Anlg Current Out 1
(+)

10

Reserved

Digital Outputs

1

16

32