Installing Control Wiring
7-3
Table 7.1 – Wiring Signal and Control I/O to the Terminal Block
No.
Signal
Factory
Default
Description
Relate
d
P
a
ram.
Analog Inputs
1
Anlg Volts In 1 (–)
1
Isolated
2
, bipolar, differential,
±10
V, 11 bit & sign, 100k ohm input
impedance.
320 -
329
2
Anlg Volts In 1 (+)
3
Anlg Volts In 2 (–)
1
Isolated
3
, bipolar, differential,
±10
V, 11 bit & sign, 100k ohm input
impedance.
4
Anlg Volts In 2 (+)
5
Potentiometer
Common
–
For (+) and (–) 10 V pot
references.
Analog Output
6
Anlg Volts Out 1 (–) Output
Freq
1
Bipolar, differential,
±10 V, 11 bit
& sign, 2k ohm minimum load.
340 -
344
7
Anlg Volts Out 1 (+)
8
Anlg Current Out 1
(–)
1
4-20 mA, 11 bit & sign, 400 ohm
maximum load.
9
Anlg Current Out 1
(+)
10
Reserved
Digital Outputs
1
16
32