Rockwell Automation SP600 User Manual Version 3.0 User Manual

Page 178

Advertising
background image

11-76

SP600 AC Drive User Manual

Selects the type of input signal being used for analog input 1 and 2.
These inputs can be configured as 0 to 10 VDC or 4 to 20 mA
inputs.

Enables/disables the square root function for each analog input.

This function should be enabled if the input signal being monitored
varies with the square of the quantity. The square root function is
scaled such that the input range is the same as the output range.
For example, if the input is set up as a unipolar voltage input, then
the input and output ranges of the square root function will be 0 to
10 volts.

320

Anlg In Config

Range:

See figure 11.35

Default:

See figure 11.35

Access:

0

Path: Inputs & Outputs>Analog Inputs

See also:

322, 323, 325, 326

Figure 11.35 – Anlg In Config (320)

0

x

x

1

x

x

x

x

x

x

x

x

x

x

x

x

10

0

1

2

3

4

5

6

7

8

9

11

12

13

14

15

1 =Current
0 =Voltage
x =Reserved

Bit #

Factory Default Bit Values

Analog In 1

Analog In 2

Nibble 1

Nibble 2

Nibble 3

Nibble 4

321

Anlg In Sqr Root

Range:

See figure 11.36

Default:

See figure 11.36

Access:

2

Path: Inputs & Outputs>Analog Inputs

See also:

Figure 11.36 – Anlg In Sqr Root (321)

0

x

x

0

x

x

x

x

x

x

x

x

x

x

x

x

10

0

1

2

3

4

5

6

7

8

9

11

12

13

14

15

1 =Enable
0 =Disable
x =Reserved

Bit #

Factory Default Bit Values

Analog In 1

Analog In 2

Nibble 1

Nibble 2

Nibble 3

Nibble 4