3 overview of sp600 features, 1 analog inputs – Rockwell Automation SP600 User Manual Version 3.0 User Manual

Page 18

Advertising
background image

2-4

SP600 AC Drive User Manual

Refer to Appendix A for drive technical specifications.

2.3

Overview of SP600 Features

This section provides an overview of the features in the SP600 AC
drive.

2.3.1 Analog Inputs

There are two general-purpose analog inputs that can be
configured either as voltage (

±

10 VDC or current (4-20 mA) inputs.

These inputs are configured via parameters to provide some
flexibility.

The analog inputs provide input signals that can be used for the
following purposes:

Provide a value to Speed Ref A (Speed Ref A Sel (90))

Provide a trim signal to Speed Ref A (Trim in Sel (117))

Table 2.2 – Power Ratings

Model

Number

F

rame

Output Amps

Nominal Power

Ratings

Input

KVA

@

575

VAC

Input

Amps

@

575

VAC

Watts

Loss

@

4 kHz

@

575

VAC

575 VAC

110% OL

Duty

150% OL

Duty

Cont

1

Min

3

Sec

kW

HP

kW

HP

-022xxxxx 2

22

25.5

34

15

20

11

15

20.1

20.2

334

-027xxxxx 2

27

33

44

18.5

25

15

20

24.7

24.8

376

-032xxxxx 3

32

40.5

54

22

30

18.5

25

29.3

29.4

408

-041xxxxx 3

41

48

64

30

40

22

30

37.4

37.6

552

-052xxxxx 3

52

61.5

82

37

50

30

40

47.5

47.7

689

-062xxxxx 4

62

78

104

45

60

37

50

58

58.2

797

-077xxxxx 5

77

85

116

55

75

-

-

72

72.3

1653

63

94

126

-

-

45

60

58

58.2

910

-099xxxxx 5

99

109

126

75

100

-

-

92.5

92.9

2243

77

116

138

-

-

55

75

72

72.3

1752

-125xxxxx 6 125

138

188

90

125

-

-

116.5

117

2386

99

149

198

-

-

75

100

92.6

93

2336

-144xxxxx 6 144

158

216

110 150

-

-

134.5

135

2836

125

188

250

-

-

90

125 116.7

117

2498