Troubleshooting the Drive

12-23

12.7

Replacement Parts

12.8

Troubleshooting the Drive Using the LCD OIM

The LCD OIM provides immediate visual notification of alarm or
fault conditions as well as the following diagnostic information:

• Entries in the fault queue

• Fault parameters

• Drive status parameters

• Selected device version and status information

• OIM version information

Table 12.14 – Stopping the Drive Results in a Decel Inhibit Fault

Indication

Cause(s)

Corrective Action

Decel Inhibit fault
screen.

LCD status line
indicates Faulted.

The bus regulation
feature is enabled and
is halting deceleration
due to excessive bus
voltage. Excess bus
voltage is normally due
to excessive
regenerated energy or
unstable AC line input
voltages.

Internal timer has halted
drive operation.

1. Reprogram bus

regulation (parameters
161 and 162) to
eliminate any Adjust
Freq selection.

2. Disable bus regulation

(parameters 161 and
162) and add a
dynamic brake.

3. Correct AC input line

instability or add an
isolation transformer.

4. Reset drive.

Table 12.15 – OIM Cables

Description

Part Number

LCD OIM Cable for remote use

RECBL-LCD

LCD OIM Extender Cable (0.3 meter)

RECBL-F03

LCD OIM Extender Cable (1 meter)

RECBL-F10

LCD OIM Extender Cable (3 meters)

RECBL-F30

LCD OIM Extender Cable (9 meters)

RECBL-F90

Table 12.16 – Drive Unit

Description

Part Number

Controller Board

313876-K01

24 V I/O Board

6SB-024A

120 V I/O Board

6SB-115B

Advertising