12-6

SP600 AC Drive User Manual

The alarm queue can be cleared using the OIM by selecting “Clr
Alarm Queue”, or by using a PC software tool.

12.4.2 Alarm Descriptions

Table 12.4 – Alarm Descriptions

Alarm

Ty

p

e

Description

Analog In
Loss

An analog input is configured for alarm on signal loss and
signal loss has occurred.

Bipolar
Conflict

Parameter 190 (Direction Mode) is set to Bipolar or
Reverse Dis and one of more of the following digital input
functions is configured: Fwd/Rev or Run Fwd. Note that
the default is Reverse Dis.

Decel
Inhibit

The drive is being inhibited from decelerating.

Dig In
ConflictA

Digital input functions are in conflict. Combinations
marked with a

will cause an alarm.

Dig In
ConflictB

Digital input functions are in conflict. Combinations
marked with a

will cause an alarm.

Dig In
ConflictC

More than one physical input has been configured to the
same input function. Multiple configurations are not
allowed for the following input functions:

DigIn Bad
Value

Unsupported function selected in Digital In”x” Sel
parameters (361-366).

Acc2 /

Dec2

Accel 2

Decel 2

Fwd / Rev

Acc2 /

Dec2

Accel 2

Decel 2

Fwd / Rev

Start

Stop–CF

Run

Run Fwd Fwd/Rev

Start

Stop–CF

Run

Run Fwd

Fwd / Rev

Forward/Reverse Run

Bus Regulation Mode B Jog Reverse

Speed Select 1

Stop Mode B

Acc2 / Dec2

UserSetBit0

Speed Select 2

OIM Control

Accel 2

UserSetBit1

Speed Select 3

Stop Mode B

Decel 2

Run Forward

Run Reverse

Jog Speed