12-14

SP600 AC Drive User Manual

Heatsink
OvrTemp

8

Heatsink temperature
exceeds a predefined
value of 90

°C (195°F).

1. Check for blocked or

dirty heat sink fins.
Verify that ambient
temperature has not
exceeded 40

°C (104°F)

NEMA Type 1 installations
or 50°C (122°F) for Open
type installations.

2. Check fan.

HW
OverCurrent

12

The drive output current
has exceeded the
hardware current limit.

Check programming.
Check for excess load,
improper DC boost setting,
DC brake volts set too
high or other causes of
excess current.

Motor dynamics cannot be
accommodated by
autotuning. Manual tuning
of the current loop
required. Consult technical
support.

Check motor lead wiring.

Incompat
MCB-PB

106

Drive rating information
stored on the power
board is incompatible
with the Main Control
board.

Load compatible version
files into drive.

I/O Comm
Loss

121

Loss of communication
to I/O board.

Cycle power.

I/O Board Fail

122

Board failure.

1. Cycle power.

2. If fault repeats, replace

I/O board

I/O Mismatch

120

Incorrect I/O board
identified.

Restore I/O board to
original configuration, or If
new configuration is
desired, reset fault.

IR Volts
Range

77

The drive autotuning
default is Calculate and
the value calculated for
IR Drop Volts is not in
the range of acceptable
values.

Re-enter motor nameplate
data.

Table 12.7 – Fault Descriptions and Corrective Actions (Continued)

Fault

No.

Ty

p

e

Description

Action