1 essential requirements for ce compliance – Rockwell Automation SP600 User Manual Version 3.0 User Manual

Page 32

Advertising
background image

About the Drive

2-18

2.4.1 Essential Requirements for CE Compliance

All conditions listed below must be satisfied for SP600 drives to
meet the requirements of EN61800-3 for the Second Environment
(Industrial).

Standard SP600 CE-compatible drive.

Grounding as described in section 5.3 if this manual.

Output power, control (I/O) and signal wiring must be braided,
shielded cable with a coverage of 75% or better, metal conduit or
equivalent attenuation.

Cable length restrictions, common mode cores and filters per
table 2.2.

Table 2.3 – SP600 AC Drive EN1800-3 EMC Compatibility

Fram

e

Drive Description

Second Environment

First Environment

Restricted

Distribution

2 Drive with any options

Restrict Motor Cable

to 30 m (98 ft)

- Restrict Motor Cable
to 150 m (492 ft)

- Install external filter

1

1

Select the Deltron Emcom (http://www.deltron--emcom.com) filter (or equivalent)
that meets your specifications from the list below.

Filter Part No. Current Filter Part No. Current
MIF306 6 A MIF350 50 A
MIF310 10 A MIF375 75 A
MIF316 16 A MIF3100 100 A
MIF323 23 A MIF3150 150 A
MIF330 30 A

3 Drive with any options

4
5
6

Drive with any options

(Not Available)