Rockwell Automation SP600 User Manual Version 3.0 User Manual

Page 141

Advertising
background image

Parameter Descriptions

11-39

.

Active stop mode. Stop Mode A is active unless Stop Mode B is
selected by a digital input. This function allows you to switch
between two stop modes using an external logic input.

Selects the source for DC Brake Level (158).

You can also select the amount of time that braking will be applied
and the magnitude of current sed for braking. This mode of braking
will generate up to 40% of the rated motor torque for braking. It is
typically used for low inertia loads.

Defines the maximum DC brake current in percentage of drive rated
current.

155
156

Stop Mode A
Stop Mode B

Range:

0 = Coast
1 = Ramp
2 = Ramp to Hold
3 = DC Brake

Default:

155: 1 = Ramp
156: 0 = Coast

Access:

1

Path: Dynamic Control>Stop/Brake Modes

See also:

157-159, 361-366

!

ATTENTION: The user must provide an external,
hardwired emergency stop circuit outside of the drive
circuitry. This circuit must disable the system in case
of improper operation. Uncontrolled machine
operation may result if this procedure is not followed.
Failure to observe this precaution could result in
bodily injury.

157

DC Brake Lvl Sel

Range:

0 = DC Brake Lvl
1 = Analog In 1
2 = Analog In 2

Default:

0 = DC Brake Lvl

Access:

1

Path: Dynamic Control>Stop/Brake Modes

See also:

155, 156, 158, 159

158

DC Brake Level

Range:

0 to (Rated Amps x 1.5) [0.1 Amps]

Default:

Rated Amps

Access:

1

Path: Dynamic Control>Stop/Brake Modes

See also:

157-159

Advertising