Parameter Descriptions

11-43

Derivative gain for the bus regulator. Used to control regulator
overshoot.

Enables/disables a feature to issue a start or run command and
automatically run at the commanded speed when drive input power
is applied.

Disabled: The drive starts on the open-to-closed transition of the
control source start input when no start inhibit conditions are
present (edge-sensitive detection).

Enabled: The drive starts when the control source start input is
closed, no start inhibit conditions are present, and power is applied
(level-sensitive detection).

Note that this feature (LevelSense Start) requires a digital input
configured for run or start and a valid start contact.

165

Bus Reg Kd

Range:

0 to 10000

Default:

1000

Access:

2

Path: Dynamic Control>Stop/Brake Modes

See also:

168

LevelSense Start

Range:

0 = Disabled
1 = Enabled

Default:

0 = Disabled

Access:

2

Path: Dynamic Control>Stop/Restart Modes

See also:

160, 163

!

ATTENTION: Be aware of the following:

• Setting parameter 168 to 1 (Enabled) immediately

applies output power to the motor when all start
conditions are met.

• If the drive is running from the terminal block,

LevelSense Start is enabled, and a fault occurs, the
drive coasts to rest and generates a fault. In this
case, resetting and clearing the fault immediately
restarts the drive without any change to the start or
stop input states.

When this function is enabled, the user must ensure
that automatic start up of the driven equipment will not
cause injury to operating personnel or damage to the
driven equipment. In addition, the user is responsible
for providing suitable audible or visual alarms or other
devices to indicate that this function is enabled and
the drive may start at any moment. Failure to observe
this precaution could result in severe bodily injury or
loss of life.