Parameter Descriptions
11-49
Defines the amount of time at or above Wake Level before a start
command is issued.
Defines the analog input signal level that will stop the drive.
Defines the amount of time at or below Sleep Level before a stop
command is issued.
181
Wake Time
Range:
0.0 to 600.0 sec [0.1 sec]
Default:
1.0 sec
Access:
2
Path: Dynamic Control>Restart Modes
See also:
178 - 183
182
Sleep Level
Range:
4.000 mA, 0.000 V to Wake Level
[0.001 mA or 0.001 V, based on Anlg In Config [320]]
Default:
5.000 mA, 5.000 V
Access:
2
Path: Dynamic Control>Restart Modes
See also:
178 - 183
183
Sleep Time
Range:
0.0 to 600.0 sec [0.1 sec]
Default:
1.0 sec
Access:
2
Path: Dynamic Control>Restart Modes
See also:
178 - 182