Parameter Descriptions

11-49

Defines the amount of time at or above Wake Level before a start
command is issued.

Defines the analog input signal level that will stop the drive.

Defines the amount of time at or below Sleep Level before a stop
command is issued.

181

Wake Time

Range:

0.0 to 600.0 sec [0.1 sec]

Default:

1.0 sec

Access:

2

Path: Dynamic Control>Restart Modes

See also:

178 - 183

182

Sleep Level

Range:

4.000 mA, 0.000 V to Wake Level
[0.001 mA or 0.001 V, based on Anlg In Config [320]]

Default:

5.000 mA, 5.000 V

Access:

2

Path: Dynamic Control>Restart Modes

See also:

178 - 183

183

Sleep Time

Range:

0.0 to 600.0 sec [0.1 sec]

Default:

1.0 sec

Access:

2

Path: Dynamic Control>Restart Modes

See also:

178 - 182