Parameter Descriptions

11-81

Selects the source of the value that drives the analog output. Refer
to table 11.4.

Sets the analog output value when the source value is at maximum.

Scaling the Analog Output

The user defines the scaling for the analog output by entering
analog output voltages into Analog Out1 Lo and Analog Out1 Hi.
These two output voltages correspond to the bottom and top of the
possible range covered by the quantity being output. The output
voltage will vary linearly with the quantity being output. The analog
output voltage will not go outside the limits defined by Analog Out1
Lo and Analog Out 1 Hi. See table 11.5.

342

Analog Out1 Sel

Range:

0 = Output Freq: Output frequency (see figure 7.3 -
Speed Reference Control Flowchart)
1 = Command Freq: Commanded frequency setpoint
(see figure 7.3 - Speed Reference Control
Flowchart)
2 = Output Amps: Total output current
3 = Torque Amps: Torque current
4 = Flux Amps: Flux current
5 = Output Power: Output power
6 = Output Volts: Output voltage
7 = DC Bus Volts: DC Bus voltage
8 = PI Reference: PI setpoint value
9 = PI Feedback: PI feedback value
10 = PI Error: Difference between PI Reference & PI
Feedback (reference - feedback)
11 = PI Output: PI output value
12 = % Motor OL: Motor overload percentage
13 = % Drive OL: Drive overload percentage
14 = Post Rmp Ref: Post Ramp Reference value (see
figure 7.3 - Speed Reference Control Flowchart)

Default:

0 = Output Freq

Access:

1

Path: Inputs & Outputs>Analog Outputs

See also:

1 - 7, 12, 135 - 138, 219, 220

343

Analog Out1 Hi

Range:

±10.000 V / 4 - 20 mA [0.001 V / .001 mA]

Default:

10.000 V / 20.000 mA

Access:

1

Path: Inputs & Outputs>Analog Outputs

See also:

342