Rockwell Automation SP600 User Manual Version 3.0 User Manual

Page 154

Advertising
background image

11-52

SP600 AC Drive User Manual

Enables/disables a feature to automatically load the present auto
frequency reference value into the OIM when Manual is selected.
Allows smooth speed transition from Auto to Manual mode. You can
adjust the manual speed setpoint from the OIM.

Enables/disables the feature that saves the present MOP (motor-
operated potentiometer) frequency reference at power down or at
stop.

Sets the rate of change of the MOP reference in response to a MOP
inputs.

193

Man Ref Preload

Range:

0 = Disabled
1 = Enabled

Default:

1 = Enabled

Access:

2

Path: Utility>OIM Ref Config

See also:

320 - 327, 361 - 366

194

Save MOP Ref

Range:

See figure 11.15

Default:

At Pwrdown

Access:

2

Path: Utility>MOP Config

See also:

Figure 11.15 – Save MOP Ref (194)

0

x

x

x

x

x

x

x

x

x

x

x

x

x

x

10

0

1

2

3

4

5

6

7

8

9

11

12

13

14

15

1 =Save
0 =Do Not Save
x =Reserved

Bit #

Factory Default Bit Values

At P

owr Do

wn

At Stop

Nibble 1

Nibble 2

Nibble 3

Nibble 4

0

195

MOP Rate

Range:

0.2 to Maximum Freq [0.1 Hz/sec]

Default:

1.0 Hz/sec

Access:

2

Path: Utility>MOP Config

See also: