11-82

SP600 AC Drive User Manual

Sets the analog output value when the source value is at minimum.

Refer to Analog Out1 Hi (343) for more information.

Table 11.5 – Analog Output Scaling

Options:

Analog Out1 Lo (344) Value Corresponds to:

Analog Out1 Hi (343)

Value Corresponds to:

Analog Out Absolut (341)

= Disabled

Analog Out Absolut (341)

= Enabled

0
1
2
3
4
5
6
7
8
9
10
11
12
13
14

Output Freq
Commanded Freq
Output Amps
Torque Amps
Flux Amps
Output Power
Output Volts
DC Bus Volts
PI Reference
PI Feedback
PI Error
PI Output
%Motor OL
%Drive OL
Post Ramp Ref

–[Maximum Speed]
–[Maximum Speed]
0 Amps
–200% Rated
0 Amps
0 kW
0 Volts
0 Volts
–100%
–100%
–100%
–100%
0%
0%
–[Maximum Speed]

0 Hz
0 Hz
0 Amps
0 Amps
0 Amps
0 kW
0 Volts
0 Volts
0%
0%
0%
0%
0%
0%
0 Hz

+[Maximum Speed]
+[Maximum Speed]
200% Rated
200% Rated
200% Rated
200% Rated
120% Rated
200% Rated
100%
100%
100%
100%
100%
100%
+[Maximum Speed]

344

Analog Out1 Lo

Range:

±10.000 V / 4 - 20 mA [0.001 V / .001 mA]

Default:

0.000 V / 4.000 mA

Access:

1

Path: Inputs & Outputs>Analog Outputs

See also:

342, 343