Rockwell Automation SP600 User Manual Version 3.0 User Manual
Page 184

11-82
SP600 AC Drive User Manual
Sets the analog output value when the source value is at minimum.
Refer to Analog Out1 Hi (343) for more information.
Table 11.5 – Analog Output Scaling
Options:
Analog Out1 Lo (344) Value Corresponds to:
Analog Out1 Hi (343)
Value Corresponds to:
Analog Out Absolut (341)
= Disabled
Analog Out Absolut (341)
= Enabled
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
Output Freq
Commanded Freq
Output Amps
Torque Amps
Flux Amps
Output Power
Output Volts
DC Bus Volts
PI Reference
PI Feedback
PI Error
PI Output
%Motor OL
%Drive OL
Post Ramp Ref
–[Maximum Speed]
–[Maximum Speed]
0 Amps
–200% Rated
0 Amps
0 kW
0 Volts
0 Volts
–100%
–100%
–100%
–100%
0%
0%
–[Maximum Speed]
0 Hz
0 Hz
0 Amps
0 Amps
0 Amps
0 kW
0 Volts
0 Volts
0%
0%
0%
0%
0%
0%
0 Hz
+[Maximum Speed]
+[Maximum Speed]
200% Rated
200% Rated
200% Rated
200% Rated
120% Rated
200% Rated
100%
100%
100%
100%
100%
100%
+[Maximum Speed]
344
Analog Out1 Lo
Range:
±10.000 V / 4 - 20 mA [0.001 V / .001 mA]
Default:
0.000 V / 4.000 mA
Access:
1
Path: Inputs & Outputs>Analog Outputs
See also:
342, 343