Rockwell Automation SP600 User Manual Version 3.0 User Manual

Page 212

Advertising
background image

12-16

SP600 AC Drive User Manual

Phase UV
Short

41

Excessive current has
been detected between
these two output
terminals.

1. Check the motor and

drive output terminal
wiring for a shorted
condition.

2. Replace drive.

Phase VW
Short

42

Phase UW
Short

43

Port 1-6 DPI
Loss

81-

86

DPI port stopped
communicating.

An attached peripheral
with control capabilities
via Logic Source Sel
(89) (or OIM control)
was removed.

The fault code indicates
the offending port
number (81 = port 1,
etc.)

1. If adapter was not

intentionally
disconnected, check
wiring to the port.
Replace wiring, port
expander, adapters,
Main Control board or
complete drive as
required.

2. Check OIM connection.

Port 1-6 Net
Loss

71-

76

The network card
connected to DPI port
stopped
communicating.

The fault code indicates
the offending port
number (71 = port 1,
etc.)

1. Check communication

adapter board for
proper connection to
external network.

2. Check external wiring to

adapter on port.

3. Verify external network

fault.

Power Loss

3

DC bus voltage
remained below 85% of
nominal for longer than
Power Loss Time (185).

Enable/disable with
Fault Config 1 (238).

Monitor the incoming AC
line for low voltage or line
power interruption.

Power Unit

70

One or more of the
output transistors were
operating in the active
region instead of
desaturation. This can
be caused by excessive
transistor current or
insufficient base drive
voltage.

1. Check for damaged

output transistors.

2. Replace drive.

Table 12.7 – Fault Descriptions and Corrective Actions (Continued)

Fault

No.

Ty

p

e

Description

Action