Sets the relay activation level for options 10-15 in Digital Out1 Sel
(380). Units are assumed to match the above selection (i.e., At Freq
= Hz, At Torque = Amps).

Sets the on delay time for the digital outputs. This is the time
between the occurrence of a condition and activation of the relay.

Sets the off delay time for the digital outputs. This is the time
between the disappearance of a condition and de-activation of the
relay.

See also:

1-4, 12, 48, 53, 137, 147, 157, 184, 218, 381-383, 385,
386

1

Any relay programmed as fault or alarm will energize (pick up) when power
is applied to the drive and de-energize (drop out) when a fault or alarm
exists. Relays selected for other functions will energize only when that
condition exists and will de-energize when the condition is removed.

2

Activation level is defined in Dig Out “x” level (381, 385).

Selects the drive signal that will energize an output relay.

380

Digital Out1 Sel

381

Dig Out1 Level

Range:

0.0 to 819.2 [0.1]

Default:

0.0

Access:

1

Path: Inputs & Outputs>Digital Outputs

See also:

380

382

Dig Out1 OnTime

Range:

0.00 to 600.00 Sec [0.01 Sec]

Default:

0.00 Sec

Access:

2

Path: Inputs & Outputs>Digital Outputs

See also:

380

383

Dig Out2 OffTime

Range:

0.00 to 600.00 Sec [0.01 Sec]

Default:

0.00 Sec

Access:

2

Path: Inputs & Outputs>Digital Outputs

See also:

380