The drive scales the value read from the analog input and converts
it to units usable for the application. The user controls the scaling by
setting parameters that associate a low and high point in the input
range with a low and high point in the target range.
Analog In 1 Hi sets the highest input value to the analog input 1
scaling block.
Sets the lowest input value to the analog input 1 scaling block. Refer
to Analog In 1 Hi (322) for more information.
322
Analog In 1 Hi
Range:
4.000 to 20.000 mA [0.001 mA]
-/+10.0 V [0.1 V]
0.0 to 10.0 V [0.1 V]
Default:
20.000 mA
Access:
0
Path: Inputs & Outputs>Analog Inputs
See also:
91, 92, 320
Analog Input Scaling Example
Speed Ref A Sel = Analog In 1
Ref. Lo (92) = 10 Hz
Ref. Hi (91) = 60 Hz
Analog In 1 Lo (323) = 0.0 V
Analog In 1 Hi (322) = 10.0 V
This is the default setting, where minimum input (0 V) represents
Ref. Lo and maximum input (10 V) represents Ref. Hi.
0
10 V
V
in
Analog In Hi
Analog In Lo
Ref Lo
10 Hz
Ref Hi
60 Hz
323
Analog In 1 Lo
Range:
4.000 to 20.000 mA [0.001 mA]
-/+10.0 V [0.1 V]
0.0 to 10.0 V [0.1 V]
Default:
4.000 mA
Access:
0
Path: Inputs & Outputs>Analog Inputs
See also:
91, 92, 320