Wiring Requirements for the Drive

4-11

Table 4.5 – AC Line Input Fuse Selection Values

Model

Number

F
r
a
m
e

Output Amps

Nominal Power Ratings

Dual

Element

Time

Delay

Fuse

Non-Time

Delay Fuse

Circuit

Breaker

575 VAC

110% OL

Duty

150% OL

Duty

575 VAC

575 VAC

575

VAC

Cont

1

Min

3

Sec

kW

HP

kW

HP

Min

Max

Min

Max

A

-022xxxxx 2

22

25.5

34

15

20

11

15

30

50

30

80

80

-027xxxxx 2

27

33

44

18.5

25

15

20

35

60

35

100

100

-032xxxxx 3

32

40.5

54

22

30

18.5

25

40

70

40

125

125

-041xxxxx 3

41

48

64

30

40

22

30

50

90

50

150

150

-052xxxxx 3

52

61.5

82

37

50

30

40

60

110

60

200

200

-062xxxxx 4

62

78

104

45

60

37

50

80

125

80

225

225

-077xxxxx 5

77

85

116

55

75

-

-

90

150

90

300

300

63

94

126

-

-

45

60

90

125

90

250

250

-099xxxxx 5

99

109

126

75

100

-

-

125

200

125

375

375

77

116

138

-

-

55

75

100

175

100

300

300

-125xxxxx 6 125

138

188

90

125

-

-

150

250

150

375

375

99

149

198

-

-

75

100 125

200

125

375

375

-144xxxxx 6 144

158

216

110

150

-

-

175

300

175

400

400

128

188

250

-

-

90

125 150

275

150

375

375