Rockwell Automation SP600 User Manual Version 3.0 User Manual
Page 155

Parameter Descriptions
11-53
Displays the present parameter access level. Refer to chapter 10 for
more information about parameter access levels.
Resets all parameter values to defaults. Option 1 resets the drive to
factory settings. Options 2 and 3 resets the drive to alternate
voltage and current rating.
Important:
On frame 5 and 6 drives, the internal fan voltage may
have to be changed when using options 2 or 3. See
section 3.1.1.4.
Loads a previously saved set of parameter values from a selected
user set location in drive non-volatile memory to active drive
memory.
An F-Key on the LCD OIM can be configured for this function. Refer
to Appendix B.
196
Param Access Lvl
Range:
0 = Basic
1 = Standard
2 = Advanced
Default:
Read Only
Access:
0
Path: Utility>Drive Memory
See also:
197
Reset To Defalts
Range:
0 = Ready
1 = Factory
2 = Low Voltage
3 = High Voltage
Default:
0 = Ready
Access:
0
Path: Utility>Drive Memory
See also:
198
Load Frm Usr Set
Range:
0 = Ready
1 = User Set 1
2 = User Set 2
3 = User Set 3
Default:
0 = Ready
Access:
1
Path: Utility>Drive Memory
See also:
199