Rockwell Automation SP600 User Manual Version 3.0 User Manual

Page 155

Advertising
background image

Parameter Descriptions

11-53

Displays the present parameter access level. Refer to chapter 10 for
more information about parameter access levels.

Resets all parameter values to defaults. Option 1 resets the drive to
factory settings. Options 2 and 3 resets the drive to alternate
voltage and current rating.

Important:

On frame 5 and 6 drives, the internal fan voltage may
have to be changed when using options 2 or 3. See
section 3.1.1.4.

Loads a previously saved set of parameter values from a selected
user set location in drive non-volatile memory to active drive
memory.

An F-Key on the LCD OIM can be configured for this function. Refer
to Appendix B.

196

Param Access Lvl

Range:

0 = Basic
1 = Standard
2 = Advanced

Default:

Read Only

Access:

0

Path: Utility>Drive Memory

See also:

197

Reset To Defalts

Range:

0 = Ready
1 = Factory
2 = Low Voltage
3 = High Voltage

Default:

0 = Ready

Access:

0

Path: Utility>Drive Memory

See also:

198

Load Frm Usr Set

Range:

0 = Ready
1 = User Set 1
2 = User Set 2
3 = User Set 3

Default:

0 = Ready

Access:

1

Path: Utility>Drive Memory

See also: