Value of volts dropped across the resistance of the motor stator.
Used only when Torque Perf Mode (53) is set to Sensrls Vect or SV
Economize. This value can be set by the Autotune procedure.
Value of amps for full motor flux. Used only when Torque Perf Mode
(53) is set to Sensrls Vect or SV Economize. This value can be set
by the Autotune procedure.
Sets the value of the voltage drop due to leakage inductance of the
motor. Used only when Torque Perf Mode (53) is set to Sensrls Vect
or SV Economize.
Sets the voltage boost level for starting and acceleration when
Custom V/Hz mode is selected in Torque Perf Mode (53).
After acceleration has stopped, the output volts per hertz is set by
the steady state operating curve.
62
IR Voltage Drop
Range:
0.0 to Motor NP Volts x 0.25 [0.1 VAC]
Default:
Motor NP Volts x 0.25
Access:
1
Path: Motor Control>Torq Attributes
See also:
53
63
Flux Current Ref
Range:
0.00 to Motor NP FLA [0.01 Amps]
Default:
Based on Drive Rating
Access:
1
Path: Motor Control>Torq Attributes
See also:
53
32
64
Ixo Voltage Drop
Range:
0.0 to Motor NP Volts [0.1 VAC]
Default:
Based on Drive Rating
Access:
2
Path: Motor Control>Torq Attributes
See also:
69
Start/Acc Boost
Range:
0.0 to Motor NP Volts x 0.25 [0.1 VAC]
Default:
Motor NP Volts x 0.25
Access:
2
Path: Motor Control>Volts per Hertz
See also:
53, 70, 83