SP600 AC Drive User Manual

If Logic Source Sel (089) is set to All Ports, the drive can only be
started when Sleep-Wake Ref (179) is greater than Sleep Level
(182). Here the sleep-wake controller remains active and does not
need to be reset. If no Start signal has been configured to reset the
sleep-wake controller, drive power can be cycled to provide the
reset function.

Sleep Level (182) and Wake Level (180) are adjustable while the
drive is "awake". If these levels are set incorrectly, the "Sleep
Config" alarm is set. If the current configuration is not corrected, the
drive will stop after the programmed Sleep Time (183).

Even though the Sleep-Wake feature is enabled, the operation of
other start modes is unchanged (e.g. if Level Sense Start is set to
Enabled, Logic Source Select is set to All Ports, and a start
command is asserted, the drive will start immediately after Sleep-
Wake Ref (179) reaches the sleep level).

The Sleep-Wake feature can be overridden in additional ways:

• The OIM Control digital input allows an attached OIM to start the

drive by overriding the Sleep-Wake Sleep signal (i.e. the analog
input is below the Sleep level). Once overridden by the OIM, the
Sleep-Wake analog input will no longer be able to start or stop the
drive until it is restarted while the analog input is above the Sleep
level.

• Jog (from an active logic source only) will override Sleep-Wake.

While Jog is active, the Sleep-Wake analog input will not be able
to Start or Stop the drive.

Selects the source of the analog input controlling the Sleep-Wake
function.

Defines the analog input signal level that will start the drive.

179

Sleep-Wake Ref

Range:

1 = Analog In 1
2 = Analog In 2

Default:

2 = Analog In 2

Access:

2

Path: Dynamic Control>Restart Modes

See also:

178 - 183

180

Wake Level

Range:

Sleep Level to 20.000 mA, 10.000 V
[0.001 mA, 0.001 V, based on Anlg In Config [320]]

Default:

6.000 mA, 6.000 V

Access:

2

Path: Dynamic Control>Restart Modes

See also:

178 - 183