Using the Start-Up Routines on the LCD OIM

9-5

9.2.2

High Speed Operation (>120 Hz)

The SP600 drive can operate at output frequencies of up to 400 Hz.
In this case, autotuning may not be able to accurately tune the
drive’s current regulator. Hardware overcurrent faults may occur,
and manual tuning using VS Utilities may be necessary. Consult
technical support if this occurs.

9.3

Start/Stop Control

The default configuration is for keypad control. You can start and
stop the drive from the local OIM.

To configure the drive for two-wire or three-wire Start/Stop control,
you must set a terminal block input to either the Run function
(2-wire) or Start function (3-wire). See section 7.5 for I/O wiring
examples.

Figure 9.3 – Start/Stop Control using the Local OIM

text

F1

ESC/

PROG

JOG

F2

F3

F4

o

I

Stop

Start

Figure 9.4 – Two-Wire and Three-Wire Start/Stop Control

24

29

25 26 27 28

Lo

gic

C

om

.

S

upp

ly C

om

.

R

un

Fu

nc

tio

n L

os

s

+2

4 V

D

C

Two-Wire Start/Stop Control

Three-Wire Start/Stop Control

24

29

25 26 27 28

Lo

gi

c Co

m

.

Su

pp

ly

Co

m.

S

tar

t

Fu

nc

tion

Lo

ss

+2

4 VD

C

St

op

(89) Logic Source Sel = Terminal Block

(361) Digital In1 Sel = Not Used

(362) Digital In2 Sel = Run

(363) Digital In3 Sel = Function Loss

(361) Digital In1 Sel = Stop

(362) Digital In2 Sel = Start

(363) Digital In3 Sel = Function Loss

(89) Logic Source Sel = Terminal Block