Rockwell Automation SP600 User Manual Version 3.0 User Manual

Page 148

Advertising
background image

11-46

SP600 AC Drive User Manual

• Issuing a stop command from any control source. (Note that

removal of a 2-wire run-fwd or run-rev command is considered a
stop command.)

• Issuing a fault reset command from any active source.

• Removing the enable input signal.

• Setting Auto Restrt Tries to zero.

• Occurrence of a fault that is not auto-resettable.

• Removing power from the drive.

• Exhausting an auto-reset/run cycle.

Sets the time between restart attempts when the auto restart
feature is enabled. Refer to Auto Rstrt Tries (174) for more
information about the auto restart feature.

Enables the Sleep-Wake function.

175

Auto Rstrt Delay

Range:

0.5 to 30.0 Sec [0.1 Sec]

Default:

1.0 Sec

Access:

1

Path: Dynamic Control>Stop/Restart Modes

See also:

174

178

Sleep-Wake Mode

Range:

0 = Disabled
1 = Direct

Default:

0 = Disabled

Access:

2

Path: Dynamic Control>Restart Modes

See also:

!

ATTENTION: Enabling the Sleep-Wake function
can cause unexpected machine motion during the
Wake mode. Do not use this function without
considering the information in the table below.
Failure to observe this precaution could result in
personal injury or damage to equipment.